8 Installation Guide for Dimming and Switching Panels
Panel Mounting
Mounting Guidelines
For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
Panel generates heat. Mount only where ambient
temperature is 32-104 °F (0-40 °C).
Relative humidity must be < 90% non-condensing.
Reinforce wall structure for panel weight and local
codes; see table.
Allow 12 in. (305 mm) clearance above and below
panel.
Mount within 7° of true vertical.
Mount panel where audible noise is acceptable.
(Internal relays click.)
Mount panel so line (mains) voltage wiring is at least
6 ft. (1.8 m) from audio or electronic equipment and
associated wiring.
Install in accordance with all national and local
electrical codes.
1
2
3
4
5
6
7
8
9
Max. Weight w/o
Packaging
Pounds (kg)
No.
Modules
Max. Heat
BTUs (Kcal)/Hr.
Surface Mounting
Lutron recommends using 1/4 in. (6 mm)
mounting bolts (maximum size accepted by
keyholes).
Reinforce wall structure as required for weight and
local codes.
Do not mount panel directly to wall board/drywall.
Recess Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8 in. (3 mm)
below finished wall surface.
Side View:
Surface Mount
Side View:
Recess Mount
Front View
Recommended Mounting Heights*
(for LCP128 systems)
Mini 45 in. (1143 mm)
Standard 25 in. (635 mm)
* Measure from floor to bottom of panel;
optimal viewing height for controller.
1
2
4
3
5
6
8
7
A
B
C
N
Load circuit wiring
Feed wiring
Do not
obstruct
vents!
PELV
(Class 2: USA)
Wiring
Air flow
Air flow
Low-
voltage
control
wiring for
TVM loads
90 (22.68)
170 (42.84)
250 (63.00)
330 (83.16)
410 (103.32)
490 (123.48)
570 (143.64)
650 (163.80)
730 (183.96)
24 (11)
35 (16)
37 (17)
68 (25)
71 (26)
74 (27)
77 (28)
80 (29)
83 (30)
CCaauuttiioonn!!
230 V panels with 13 A circuit
breakers are intended for industrial or
commercial use only.
CCaauuttiioonn!!
This equipment is air-cooled. Vents
must not be blocked or you will void the
warranty.
LP8/32-1204ML-20 shown