Installation Guide for Switching Panels 11
Wiring
(continued)
H
SH
H
SH
H
SH
H
SH
H
SH
Panel with Branch Circuit Breakers: Feed and Load Wiring
(120/277/347 V only)
Bypass jumpers -
do not remove
Load
Neutral bus
Neutral bus
Main lugs
Branch circuit
breakers for
temporary
lighting
Wiring Tips
Wire the switching panel similar
to wiring a lighting distribution
panel:
Run feed and load wiring. No
other wiring or assembly
required.
The switching panel can provide
temporary lighting:
Wire all loads.
Leave the bypass jumpers in
place.
Use branch circuit breakers at
the distribution panel to switch
lights on and off.
Wire Sizes
120 V #4 AWG to 250 KCMIL (MCM) (25-185 mm
2
)
277 V #4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
2
)
347 V #4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
2
)
Feed Wiring
Switched Hot/Live
#14-#10 AWG
(2.5-4.0 mm
2
)
Load Neutral
#14-#10 AWG
(2.5-4.0 mm
2
)
Typical switch leg
XP12-1204ML-20 shown